Standard operating instructions for gas fire extinguishing installations. Brief instructions for operating the installations of the facility

OJSC "SIBNEFT-NOYABRSKNEFTEGAZ"

TERRITORIAL OIL PRODUCTION PROJECT

"KHOLMOGORNEFT"

I N S T R U C T I O N

on the operation of the water system

fire extinguishing equipment UPSVG-2 TsPPN-2.

Noyabrsk

2003

OJSC "SIBNEFT - NOYABRSKNEFTEGAZ"

TERRITORIAL OIL PRODUCTION PROJECT “KHOLMOGORNEFT”

APPROVED I APPROVED

Chairman of the trade union committee Head of TPDN

TPDN "Kholmogorneft" "Kholmogorneft"

___________ O.F. Yushko _______ S.Yu. Rusakov

"" _______2003 "___" ________ 2003

Head of PCH-130 OGPS-9

THEM. Miroshnichenko

"__" __________2003

I N S T R U C T I O N

on the operation of the water system

fire extinguishing equipment UPSVG-2 TsPPN-2.

I.General situation.

This instruction has been developed on the basis of the “Fire Safety Rules in Russian Federation"(PPB 01-03) and "Fire Safety Rules in oil industry» PPBO-85.

1.1. The head of the workshop, by his order, appoints someone responsible for the safe operation of the water fire extinguishing system.

1.2. The person responsible for technical operation regularly carries out inspections, checks and tests according to the schedule, together with the service organization of the entire water fire extinguishing system.

II. Purpose and device of water extinguishing.

2.1. The water fire extinguishing system is designed for external extinguishing of buildings and installation structures, as well as for supplying water to the tank farm for cooling the tanks by irrigation in the event of an oil fire in them.

2.2. The installation consists of a ring pipeline with fire hydrants designed by Doroshevsky in the amount of 13 pieces, located along the perimeter of the water supply system and the tank farm and connected to the water supply system using valves No. 551/1, 551/2, 557, 558, valve units for supplying water along directions.

2.2.1. The water fire extinguishing system is dry pipe, laid above ground with heat traces. On fire water supply At high turning points, valves are installed to release air, and at low points, vents are installed to release water.

2.2.2. Block box for fire pumps – pumps K 100/65 – 2 pcs., for supplying water from fire fighting pumps – 1.2 to the fire ring.

2.2.3. The water supply, fire hydrants, fittings are thermally insulated along with heat traces with mineral wool mats.

2.2.4. All RVS-5000 are equipped with a stationary wall cooling unit, consisting of an irrigation ring and a supply dry pipe. The dry pipe is connected through a valve to the ring fire water pipeline. The irrigation ring consists of four parts, each part is supplied with water through a separate supply dry pipe. In addition, a dry pipe was installed to cool the tank walls from mobile equipment through the GM-80 connecting heads.

III. Preparing the water fire extinguishing system for operation.

3.1. When preparing the water fire extinguishing system for operation, it is necessary to check the position of manual and electric valves:

3.1.1. Valves connecting the water fire extinguishing system to the water supply system No. 550, 551/1, 551/2, 552 must always be open.

3.1.2. Electric valves No. 554, 555, 558 and valves on bypass lines No. 553, 556, 557 must be closed.

3.1.2. Fire ring valves Nos. 560, 561, 562, 563, 564, 565, 566, 567, 568 must be open.

3.1.3. All water supply valves for cooling tanks must be closed:

RVS-5000 No. 1 - No. 569/1-572/1, 569/1d-572/1d;

RVS-5000 No. 2 - No. 569/2-572/2, 569/2d-572/2d;

RVS-5000 No. 3 - No. 569/3-572/3, 569/3d-572/3d;

RVS-5000 No. 4 - No. 569/4-572/4, 569/4d-572/4d.

3.1.4. Valves No. 1, 2, 4, 14 on fire fighting stations – 1, 2 must be open

3.2. Check the pressure in the PPD system, it should be no lower than 5 kgf/cm 2

IV. Putting the water fire extinguishing system into operation.

4.1. To put the water fire extinguishing system into operation, you must turn on the K 100/65 pump to fill the system with water.

4.2. The pressure in the system must be maintained at least 5 kgf/cm 2 by regulating the flow through valves Nos. 554, 555, 558 at the point of connection to the RPM system.

4.3. In case of fire on the RVS-5000, open valves No. 569-572 of the burning and cooled tanks. If more intensive cooling is necessary, we connect the fire equipment using the GM-80 connecting heads and open the corresponding valves (No. 569d-572d) of the additionally cooled tank.

4.4 Additional cooling of the tanks is possible by connecting

to the nearest safely located fire hydrants (PG 1-10)

The operation of fire automatics installations means their use for detecting or extinguishing fires, as well as their maintenance and repair. When operating AUP, APS, a set of measures is carried out that ensure:

technically correct use installations, i.e. application when detecting or extinguishing a fire, in extinguishing mode;

proper storage;

timely and high-quality technical maintenance in order to maintain the installation in good working order;

timely and high-quality repairs;

Maintenance is understood as a set of works that provides control technical condition, extending the service life. Maintenance activities are divided into four groups:

preparing the installation for use after activation or repair, including refueling and loading operations (replacement of triggered or damaged sprinklers, etc.);

technical condition monitoring;

prevention;

routine repairs in order to maintain the reliability and durability of installations.

Technical condition monitoring is carried out to assess the ability of installations to perform specified functions. This ability is assessed by values certain parameters. If the values ​​of these parameters correspond to the passport values, the installation is considered to be in good condition.

In case of deviation from the norms, the installation is faulty, because it cannot provide satisfactory performance specified functions. Thus, monitoring the state of installations comes down to compiling true ones, i.e. measured at the installation, values, parameters with their nominal values. As a result of the comparison, a conclusion is drawn about the technical condition of the installation and the possibility of its further use.

Maintenance is divided into daily, monthly, quarterly, and annual. During daily maintenance the following scope of work is performed:

monitoring the condition of pipeline painting;

control over compliance with permissible distances (no more than two meters) from sprinklers to stored materials;

external inspection of control units (control and starting units, valves);

checking pressure gauges above and below the control and starting unit (the difference should not exceed 0.05);

operation of pumps and compressors in accordance with the instructions (certificates) of the manufacturers. The inspection results for each item are recorded in the “installation operation” log.

During monthly maintenance, daily work is carried out maintenance, and also perform the following operations:

inspection and preventive maintenance related to electrical equipment of installations;

checking the voltage of the main and backup power sources, inputs to automatic switches, inputs of automatic switches in the alarm circuit;

checking the functionality of electrical equipment circuits in remote and automatic modes;

inspection and preventive maintenance of all installation communications

checking pumps and their fittings, pressure - according to pressure gauges;

checking control and starting devices.

Quarterly maintenance includes monthly maintenance operations, in addition, the following work is performed:

checking the condition and fastening of the pipeline and sprinklers;

checking the operation of the ECM using a control pressure gauge;

turning the shafts of electric pump motors manually.

The annual includes quarterly maintenance activities and in addition to this:

leak test check valves and valves;

inspection and inspection of control measuring instruments within the time limits specified in the factory instructions;

replacement or repair of worn parts;

random check of water yield of sprinklers;

measurement of ground loop resistance.

In addition, there are types of maintenance work that must be carried out every 3 years. These include:

annual maintenance operations;

eliminating leaks in the system, repairing equipment fastenings;

touch-up of equipment;

repair of grounding devices;

measurement of installation drive insulation;

pump inspection, shut-off valves;

flushing the system.

AUP OPERATING INSTRUCTIONS.

GENERAL INSTRUCTIONS

Acceptance of the AUP for operation must be carried out by representatives of:

energy enterprises (chairman);

design, installation and commissioning organizations;

state fire supervision.

The commission's work program and acceptance certificate must be approved by the chief technical manager of the enterprise.

SAFETY MEASURES

When operating technological equipment of water fire extinguishing installations, personnel of energy enterprises must comply with the relevant safety requirements specified in PTE, PTB, as well as in factory passports and operating instructions for specific equipment.

During maintenance and repair of the automatic control system, when visiting a room protected by the automatic control system, the automatic control of a specific distribution pipeline in this direction must be switched to manual (remote) until the last person leaves the room.

Pressure testing of pipelines with water should be carried out only according to an approved program, which should include measures to ensure the protection of personnel from possible rupture of pipelines. It is necessary to ensure complete removal of air from the pipelines. Combining crimping work with other work in the same room is prohibited. If pressure testing is carried out by contractors, then the work is performed according to the work permit. The performance of these works by operational or maintenance personnel of the energy enterprise is formalized by written order.

Before starting work, personnel involved in pressure testing must undergo workplace safety training.

There should be no unauthorized persons in the room during pressure testing. Pressure testing must be carried out under control responsible person.

Repair work on process equipment must be carried out after removing the pressure from this equipment and preparing the necessary organizational and technical measures established by the current safety regulations.

PREPARATION FOR WORK AND CHECKING TECHNICAL CONDITION

FIRE FIGHTING UNITS

The foam fire extinguishing installation consists of:

source of foam supply (reservoir);

fire pumps (designed for taking and supplying solution into pressure pipelines);

suction pipelines (connecting the water source with fire pumps);

pressure pipelines (from the pump to the control unit);

distribution pipelines (laid within the protected premises);

control units installed at the end of pressure pipelines;

irrigators.

In addition to the above, based on design solutions, the following may be included in the fire extinguishing installation diagram:

a tank with a foaming agent solution for filling fire pumps;

air tank for maintenance constant pressure in the fire extinguishing installation network;

compressor for replenishing the pneumatic tank with air;

drain valves;

check valves;

dosing washers;

pressure switch;

pressure gauges;

vacuum gauges;

level gauges for measuring the level in tanks and pneumatic tanks;

other signaling, control and automation devices.

After graduation installation work suction, pressure and distribution pipelines must be flushed and hydraulically tested. The results of washing and pressure testing must be documented.

If possible, the effectiveness of the fire extinguishing installation should be checked by organizing extinguishing an artificial source of fire.

When flushing pipelines, water should be supplied from their ends towards the control units (in order to prevent clogging of pipes with a smaller diameter) at a speed 15-20% higher than the speed of the solution in case of fire (determined by calculations or recommendations of design organizations). Flushing should be continued until a steady appearance clean water. If it is impossible to flush certain sections of pipelines, it is allowed to blow them with dry, clean, compressed air or inert gas.

Hydraulic testing of pipelines must be carried out under a pressure equal to 1.25 working pressure (P), but not less than P+0.3 MPa, for 10 minutes.

To disconnect the tested section from the rest of the network, it is necessary to install blind flanges or plugs. It is not allowed to use existing control units, repair valves, etc. for this purpose.

After 10 minutes of testing, the pressure should be gradually reduced to working pressure and a thorough inspection of all welded joints and adjacent areas should be carried out.

The pipeline network is considered to have passed the hydraulic test if no signs of rupture, leakage or drops are found in welded joints and on the base metal, visible residual deformations.

Pressure should be measured with two pressure gauges.

Flushing and hydraulic testing of pipelines must be carried out under conditions that prevent them from freezing.

It is prohibited to fill open trenches with pipelines that have been exposed to severe frosts, or to fill such trenches with frozen soil.

Automatic water fire extinguishing installations must operate in automatic start mode. During the period of personnel presence in cable structures (bypass, repair work, etc.), the start-up of installations must be switched to manual (remote) activation.

MAINTENANCE OF FIRE FIGHTING INSTALLATIONS

Persons responsible for the operation, overhaul and current repairs of process equipment of a fire extinguishing installation are appointed by the head of the energy enterprise, who also approves schedules for technical supervision and repair of equipment.

The person responsible for the constant readiness of the process equipment of a fire extinguishing installation must have a good knowledge of the design principle and operating procedure of this equipment, and also have the following documentation:

project with changes made during installation and commissioning of the fire extinguishing installation;

factory passports and operating instructions for equipment and devices;

this Standard Instruction and local operating instructions for process equipment;

acts and protocols for conducting installation and commissioning work, as well as testing the operation of technological equipment;

schedules for maintenance and repair of process equipment;

“Logbook of maintenance and repair of fire extinguishing installations.”

Any deviations from the scheme adopted by the project, replacement of equipment, additional installation of sprinklers or their replacement with sprinklers with a larger nozzle diameter must be previously agreed upon with the design institute - the author of the project.

To monitor the technical condition of the process equipment of the fire extinguishing installation, a “Logbook of maintenance and repair of the fire extinguishing installation” must be kept, which must record the date and time of the inspection, who carried out the inspection, detected malfunctions, their nature and the time of their elimination, the time of forced shutdown and startup fire extinguishing installations, testing of the operation of the entire installation or individual equipment.

At least once a quarter, the chief technical manager of the enterprise must familiarize himself with the contents of the magazine against receipt.

To check the readiness and effectiveness of the AUVP, a complete audit of the technological equipment of this installation must be carried out once every three years.

During the inspection, in addition to the main work, pressure testing of the pressure pipeline is carried out and in two or three directions, washing (or purging) and pressure testing of distribution pipelines located in the most aggressive environment (dampness, gas contamination, dust) is carried out.

If deficiencies are discovered, it is necessary to develop measures to ensure their complete elimination in a short time.

Automatic installation fire extinguishing systems in accordance with the schedule approved by the head of the relevant workshop, but at least once every three years must be tested (tested) according to a specially developed program with their actual commissioning, provided that this does not entail a shutdown of the technological equipment or the entire production process . During testing on the first and last sprinklers, the water pressure and irrigation intensity should be checked.

Testing should be carried out for 1.5-2 minutes with the inclusion of working drainage devices.

Based on the test results, a report or protocol must be drawn up, and the fact of testing must be registered in the “Logbook of maintenance and repair of the fire extinguishing installation.”

Checking the operation of the AUVP or individual species equipment should be carried out during repair, maintenance of the protected premises and technological installation.

For storing spare equipment, equipment parts, as well as devices, tools, materials, devices necessary for control and organization repair work AUVP, a special room must be allocated.

The technical capabilities of the AUVP should be included in operational plan extinguishing a fire at this power plant. During the fire drills it is necessary to expand the circle of personnel who know the purpose and structure of the AUVP, as well as the procedure for putting it into operation.

Personnel servicing AUVP compressors and pneumatic tanks must be trained and certified in accordance with the requirements of the Gosgortekhnadzor rules.

The person responsible for the operation of the process equipment of a fire extinguishing installation must organize training with the personnel allocated to control the operation and maintenance of this equipment.

In the premises of the AUVP pumping station, the following must be posted: instructions on the procedure for putting pumps into operation and opening shut-off valves, as well as circuit and technological diagrams.

Entrances to the building (room) of the pumping station and fire extinguishing installation, as well as approaches to pumps, pneumatic tanks, compressors, control units, pressure gauges and other equipment of the fire extinguishing installation, must always be free.

In an operating fire extinguishing installation, the following must be sealed in the operating position:

hatches of tanks and containers for storing water supplies;

control units, valves and manual taps;

pressure switch;

drain taps.

After the fire extinguishing system has been activated, its functionality must be fully restored within 24 hours.

Checking the water level in the tank should be carried out daily and recorded in the “Logbook of maintenance and repair of the fire extinguishing installation.” If the water level decreases due to evaporation, it is necessary to add water, if there are leaks, determine the location of damage to the tank and eliminate the leaks.

The serviceability of the automatic level gauge in the tank must be checked at least once every three months at positive temperatures, monthly - at negative temperature and immediately in case of doubt about proper work level gauge.

Tanks must be closed to access by unauthorized persons and sealed; the integrity of the seal is checked during the inspection of the equipment, but at least once a quarter.

The water in the tank should not contain mechanical impurities that could clog pipelines, dosing washers and sprinklers.

To prevent water from rotting and blooming, it is recommended to disinfect it with bleach at the rate of 100 g of lime per 1 m of water.

The water in the tank must be replaced annually in the fall. When replacing water, the bottom and inner walls of the tank are cleaned of dirt and build-up, and damaged paint is restored or completely renewed.

Before the onset of frost in buried tanks, the gap between the lower and upper hatch covers must be filled with insulating material.

Once a quarter, the condition of the inputs, shut-off valves, measuring instruments and water intake well is checked.

Before the onset of frost, the fittings in the water intake well must be inspected, repaired if necessary, and the well insulated.

Before testing the pumps, it is necessary to check: the tightness of the seals; lubricant level in bearing baths; correct tightening of foundation bolts, pump cover nuts and bearings; connections of the piping on the suction side and the pumps themselves.

Once a month, pumps and other equipment of the pumping station must be inspected and cleaned of dust and dirt.

Each fire pump must be turned on at least twice a month to create the required pressure, which is recorded in the operational log.

At least once a month, the reliability of transferring all fire pumps to the main and backup power supply should be checked and the results recorded in the operational log.

If there is a special tank for filling pumps with water, the latter must be inspected and painted annually.

Once every three years, pumps and motors in accordance with clause 5.1.5 of this Standard instructions, must undergo an audit, during which all existing deficiencies are eliminated. Repair and replacement of worn parts, checking of seals are carried out as necessary.

The pumping station premises must be kept clean. When not on duty, it must be locked. One of the spare keys must be stored on the control panel, as indicated on the door.

Once a quarter you need to check:

absence of leaks and deflections of pipelines;

the presence of a constant slope (at least 0.01 for pipes with a diameter of up to 50 mm and 0.005 for pipes with a diameter of 50 mm or more);

condition of pipeline fastenings;

no contact with electrical wires and cables;

condition of painting, absence of dirt and dust.

Detected deficiencies that may affect the reliability of the installation must be corrected immediately.

The pressure pipeline must be in constant readiness for action, i.e. filled with water and under operating pressure.

For AUP transformers and cable structures in shut-off and starting devices should be used steel reinforcement, electrified valves with automatic start brands 30s 941nzh; 30s 986nzh; 30s 996nzh with a working pressure of 1.6 MPa, repair valves with manual drive brand 30s 41nzh with a working pressure of 1.6 MPa.

The condition of control units and shut-off valves, the presence of seals, and pressure values ​​before and after control units must be monitored at least once a month.

An inspection must be carried out once every six months electrical diagram activation of the control unit with its automatic activation from the fire detector when the valve is closed.

The installation site of the control unit must be well lit, the inscriptions on the pipelines or special stencils (node ​​number, protected area, type of sprinklers and their quantity) must be made with indelible bright paint and be clearly visible.

All damage to valves, valves and check valves that may affect the reliability of the fire extinguishing installation must be repaired immediately.

As water sprinklers for automatic fire extinguishing transformers use OPDR-15 sprinklers with a working water pressure in front of the sprinklers in the range of 0.2-0.6 MPa; For automatic fire extinguishing of cable structures, DV, DVM sprinklers with a working pressure of 0.2-0.4 MPa are used.

When inspecting switchgear equipment, but at least once a month, sprinklers must be inspected and cleaned of dust and dirt. If a malfunction or corrosion is detected, measures must be taken to eliminate it.

When carrying out repair work, sprinklers must be protected from plaster and paint (for example, with plastic or paper caps, etc.). Traces of paint and mortar found after repair must be removed.

It is prohibited to install plugs or plugs in place of faulty sprinklers.

To replace faulty or damaged sprinklers, a reserve of 10-15% of the total number of installed sprinklers should be created.

Putting the pneumatic tank into operation must be done in the following sequence:

fill the pneumatic tank with water to approximately 50% of its volume (check the level using the water gauge glass);

turn on the compressor or open the valve on the compressed air pipeline;

raise the pressure in the pneumatic tank to operating pressure (controlled by a pressure gauge), after which the pneumatic tank is connected to the pressure pipeline, creating working pressure in it.

Every day you should carry out an external inspection of the air tank, check the water level and air pressure in the air tank. When the air pressure decreases by 0.05 MPa (relative to the working one), it is pumped up.

Once a week the compressor is tested at idle.

Maintenance of the air tank and compressor, carried out once a year, includes:

emptying, inspecting and cleaning the air tank;

removal and testing on a bench safety valve(if faulty, replace with a new one);

painting the surface of the air tank (indicate the date of repair on the surface);

detailed inspection of the compressor (replace worn parts and fittings);

fulfillment of all other technical requirements stipulated by the factory passports and operating instructions for the pneumatic tank and compressor.

Disconnecting the pneumatic tank from the fire extinguishing installation circuit is prohibited.

The inspection of the pneumatic tank is carried out by a special commission with the participation of representatives of Gosgortekhnadzor, local bodies of the State Fire Supervision and the given energy enterprise.

The correct operation of pressure gauges installed on pneumatic tanks should be checked once a month; those installed on pipelines should be checked once every six months.

A complete check at the fire extinguishing installation of all pressure gauges with their sealing or branding must be carried out annually in accordance with the current regulations.

ORGANIZATION AND REQUIREMENTS FOR REPAIR WORK

When repairing process equipment of a fire extinguishing installation, one should, first of all, be guided by the requirements of the passport, the plant’s instructions for operating specific equipment, the requirements of relevant standards and technical specifications, as well as the requirements of this instruction.

When replacing a section of pipeline at a bend, the minimum radius of the internal bend curve steel pipes When bending them in a cold state, there must be at least four outer diameters, and in a hot state - at least three.

There should be no folds, cracks or other defects on the curved part of the pipe. Ovality in places of bending is allowed no more than 10% (determined by the ratio of the difference between the largest and smallest outer diameters of the bent pipe to the outer diameter of the pipe before the bend).

The difference in thickness and displacement of the edges of joined pipes and pipeline parts should not exceed 10% of the wall thickness and should not exceed 3 mm.

Before welding, the edges of the pipe ends to be welded and the surfaces adjacent to them must be cleaned of rust and dirt to a width of at least 20 mm.

Welding of each joint must be performed without interruption until the entire joint is completely welded.

The welded pipe joint must be rejected if the following defects are detected:

cracks extending to the surface of the weld or base metal in the welding zone;

sagging or undercuts in the transition zone from the base metal to the deposited metal;

burns;

unevenness of the weld seam in width and height, as well as its deviations from the axis.

In particularly damp rooms with a chemically active environment, pipeline fastening structures must be made of steel profiles with a thickness of at least 4 mm. Pipelines and fastening structures must be coated with protective varnish or paint.

Pipeline connections during open installation must be located outside walls, partitions, ceilings and other building structures of buildings.

Fastening pipelines to building structures buildings should be made with normalized supports and suspensions. Welding pipelines directly to metal structures buildings and structures, as well as elements of technological equipment is not allowed.

Welding of supports and hangers to building structures must be carried out without weakening them mechanical strength. Sagging and bending of pipelines is not allowed.

Each pipeline bend longer than 0.5 m must have a fastening. The distance from hangers to welded and threaded joints of pipes must be at least 100 mm.

Newly installed sprinklers must be cleaned of preservative grease and tested with a hydraulic pressure of 1.25 MPa (12.5 kgf/cm2) for 1 minute. Average term The service life of sprinklers is determined to be at least 10 years.

VII. MONITORING COMPLIANCE WITH STANDARDS, RULES AND SAFETY REQUIREMENTS DURING OPERATION OF ASPS (ASPS)

36. Responsibility for organizing the operation of ASPT (ASPS) is assigned to the managers of facilities that are protected by fire automatic equipment.

37. In the process of a detailed inspection of the ASPT (ASPS), a representative of the State Border Service authorities checks the availability of the necessary technical documentation for the installation, analyzes its condition, conducts an external inspection and performance monitoring.

38. Requirements for operational technical documentation for ASPT (ASPS).

38.1. For each ASPT (ASPS), an order or instruction must be issued for the enterprise (organization), appointing:

  • the person responsible for the operation of the installation;
  • operational (duty) personnel for round-the-clock monitoring of the operating condition of the installations.
  • 38.2. For each ASPT, operating instructions must be developed for those responsible for the operation of the installation and for the personnel servicing this installation, taking into account the specifics of the protected premises, approved by the management of the enterprise and agreed upon with the organization performing maintenance and repair of the ASPT.

    The person responsible for the operation of the ASPT must promptly inform the local State Fire Service authorities about failures and operation of the installations.

    38.3. Operational (duty) personnel must have and fill out the “Installation Failure Log” (Appendix 33).

    38.4. An enterprise that carries out maintenance and repair of fire protection equipment must have a license from the State Fire Service of the Ministry of Internal Affairs for “Installation, adjustment, repair and maintenance of fire protection equipment and systems.”

    Maintenance and repair may be carried out by facility specialists with appropriate qualifications. In this case, the procedure for carrying out maintenance and repair work must comply with these methodological recommendations.

    Restoring the functionality of the ASPT or ASPS after its operation or failure should not exceed:

  • for Moscow, St. Petersburg, administrative centers of autonomous entities within the Russian Federation - 6 hours;
  • for other cities and towns - 18 hours.
  • 38.5. An “Agreement for maintenance and repair of automatic fire extinguishing installations” must be concluded and valid between the operating organization and the enterprise performing maintenance and repair.

    38.6. The control room premises must contain instructions on the procedure for the duty dispatcher to act upon receiving alarm signals.

    38.7. Acceptance of ASPT for maintenance and repair must be preceded by a primary inspection of the installation in order to determine its technical condition.

    The initial examination of the ASPT should be carried out by a commission, which includes a representative of the State Fire Service bodies.

    Based on the results of the ASPT inspection, a “Certificate for the initial inspection of automatic fire extinguishing installations” (Appendix 34) and a “Report for the work performed on the primary inspection of automatic fire extinguishing installations” (Appendix 35) should be drawn up.

    38.8. For an installation accepted for maintenance and repair, after concluding the contract, the following must be filled out:

  • passport of the automatic fire extinguishing installation (Appendix 36);
  • logbook for recording maintenance and repair of automatic fire extinguishing installations (Appendix 37). It must record all maintenance and repair work, including quality control. One copy of this log must be kept by the person responsible for operating the installation, the second - in the organization performing maintenance and repair. The log must also indicate the safety briefing of personnel performing maintenance and repair responsible for operating the installation. The pages of the magazine must be numbered, laced and sealed with the seals of organizations servicing ASPT and carrying out maintenance and repair;
  • maintenance and repair schedule (Appendix 38). The procedure for maintenance and repair of ASPT, as well as the period for eliminating installation failures, must comply with these methodological recommendations. The list and frequency of maintenance work must comply with standard ASPT (ASPS) maintenance regulations (Appendices 39-43);
  • scroll technical means included in ASPT and subject to maintenance and repair (Appendix 44);
  • technical requirements defining the performance parameters of ASPT (Appendix 45).
  • 38.9. The enterprise must have the following technical documentation:

  • ASPT initial examination report;
  • act for the work performed on the primary inspection of ASPT;
  • maintenance and repair agreement;
  • maintenance and repair schedule;
  • technical requirements defining the performance parameters of ASPT;
  • list of technical equipment included in ASPT and subject to maintenance and repair;
  • call log;
  • ASPT technical inspection report;
  • project at ASPT;
  • passports, certificates for equipment and instruments;
  • list of installed equipment, components, devices and automation equipment;
  • passports for charging installation cylinders gas fire extinguishing;
  • installation operating instructions;
  • maintenance and repair work log;
  • duty schedule of operational (duty) personnel;
  • log of duty acceptance by operational personnel;
  • log of weighing (control) of cylinders with fire extinguishing composition of gas fire extinguishing installations.
  • 38.10. All necessary documentation for the ASPT (or copies thereof) must be kept by the person responsible for the operation of the ASPT.

    39. During an external inspection of the ASPT and the premises protected by it, it is necessary to verify compliance with the project:

  • characteristics of the protected premises and its flammable load;
  • modifications of sprinklers of fire extinguishing installations, methods of their installation and placement;
  • cleanliness of sprinklers;
  • pipelines of installations (the use of pipelines of fire extinguishing installations for hanging, attaching, connecting equipment that is not related to fire extinguishing equipment is not allowed);
  • light and beep ization located in the control center;
  • telephone communication between the control center and the fire department of an enterprise or locality.
  • 40. In the process of monitoring compliance with norms, rules and safety requirements during the operation of ASPT, it is necessary to check their performance and conduct tests (without releasing fire extinguishing agent), confirming the installation of the main signals and commands.

    41. Features of monitoring water and foam fire extinguishing installations during operation
    41.1. When conducting an inspection of the technical condition of water and foam fire extinguishing installations, it is necessary to be guided by GOST R 50680-94 "Automatic water fire extinguishing installations. General technical requirements. Test methods", GOST R 50800-95 "Automatic foam fire extinguishing installations. General technical requirements. Test methods" and requirements of these rules.

    41.2. During the inspection of water and foam fire extinguishing installations, the following should be checked:

    41.2.1. Condition of sprinklers (in places where there is a danger of mechanical damage, sprinklers must be protected by reliable fences that do not affect the irrigation map and the distribution of heat flows).

    41.2.2. Standard sizes of sprinklers (within each distribution pipeline (one section) sprinklers with outlet openings of the same diameter must be installed).

    41.2.4. Availability of a supply of sprinklers (must be at least 10% for each type of sprinklers installed on distribution pipelines, for their timely replacement during operation).

    41.2.5. Protective coating pipelines (in rooms with a chemically active or aggressive environment they must be protected with acid-resistant paint).

    41.2.6. Availability of a functional diagram for tying control nodes (each node must have a functional diagram piping, and in each direction - a plate indicating the operating pressures, protected premises, the type and number of sprinklers in each section of the system, the position (state) of the shut-off elements in standby mode).

    41.2.7. The presence of devices on tanks for storing an emergency supply of water for fire extinguishing purposes, eliminating the consumption of water for other needs.

    41.2.8. Availability of a reserve stock of foaming agent (a 100% reserve stock of foaming agent must be provided).

    41.2.9. Providing the pumping station premises with telephone communication with the control center.

    41.2.10. The presence at the entrance to the pumping station premises of a sign “Fire extinguishing station” and a constantly functioning light board with a similar inscription.

    41.2.11. Availability of clearly and neatly executed piping diagrams of the pumping station and a basic diagram of the fire extinguishing installation posted in the pumping station premises. All indicating measuring instruments must have inscriptions about operating pressures and the permissible limits of their measurements.

    41.2.12. Duration of installation testing (testing of water and foam fire extinguishing installations during their operation should be carried out at least once every 5 years).

  • install plugs and plugs to replace broken or faulty sprinklers, as well as install sprinklers with anything other than the specified project documentation, melting temperature of the castle;
  • store materials at a distance of less than 0.6 m from sprinklers;
  • use the pipelines of fire extinguishing installations for hanging or fastening any equipment;
  • connect production or plumbing equipment to the supply pipelines of the fire extinguishing installation;
  • install shut-off valves and flange connections on supply and distribution pipelines;
  • use internal fire hydrants installed on the sprinkler network for purposes other than fire suppression;
  • use compressors for purposes not related to ensuring the operability of the installation.
  • 42. Features of monitoring gas fire extinguishing installations during operation
    42.1. In the process of monitoring the UGP during operation, it is necessary to:

  • carry out an external inspection components installations for the absence of mechanical damage, dirt, fastening strength, presence of seals;
  • check the working position of shut-off valves in the incentive network and launch cylinders;
  • check the main and backup power sources, check the automatic switching of power from the working input to the backup one;
  • control the quantity of waste fuel by weighing or pressure control (for centralized UGP - the main and reserve quantity of waste fuel, for modular UGP - the number of waste fuel and the availability of its stock);
  • check the operability of the components of the installation (technological part, electrical part);
  • check the operation of the installation in manual (remote) and automatic modes;
  • check the availability of metrological verification of instrumentation;
  • measure the resistance of protective and working grounding;
  • measure insulation resistance electrical circuits;
  • check the availability and validity period of the technical certification of the components of the UGP operating under pressure.
  • 42.2. Control and testing of the UGP must be carried out without releasing the fire extinguishing agent according to the methods set out in GOST R 50969-96.

    42.3. Control of the mass (pressure) of the state gas pump, control of the gas pressure in the incentive cylinders must be carried out within the time limits established by the TD at the UGP, with a note in the log. The requirements for GOS and propellant gas used when refueling (pumping) the UGP must be the same as for the initial refueling.

    42.4. Fire extinguishing stations must be equipped and maintained in a condition consistent with design decisions.

    42.5. If during the operation of the UGP, its operation or failure occurs, the operability of the UGP must be restored (filling with GOS, propellant gas, replacing modules, squibs in launch cylinders, distribution devices, etc.) in established deadlines and the corresponding journal entries were made.

    In the case of using GOS from the UGP stock, it must be restored simultaneously with the restoration of the UGP’s operability.

    43. Features of installation control aerosol fire extinguishing during operation
    43.1. When inspecting objects protected by UAP, it is necessary to monitor compliance with a number of regulatory requirements.

    43.1.1. The requirements of the maintenance regulations for the inspected UAP must not be lower than the requirements of the "Standard Maintenance Regulations for Aerosol Fire Extinguishing Installations".

    43.1.2. If mechanical damage is possible at the installation site of the GOA, then they must be fenced.

    43.1.3. The installation locations of the GOA and their orientation in space must correspond to the project.

    43.1.4. The GOA must have seals or other devices confirming its integrity.

    43.1.5. Combustible load of the room protected by the UAP, its leakage and geometric dimensions must correspond to the project.

    43.1.6. There should be no flammable materials on the surface of the GOA and in the area affected by the high-temperature aerosol jet.

    43.1.7. Electrical wires intended to supply an electrical impulse to the GOA starting device must be laid and protected from thermal and other influences in accordance with the design.

    43.1.8. The GOA reserve must correspond to the project.

    43.1.9. Light and sound alarms must be in working order in the protected premises and in the duty post premises.

    43.1.10. There must be instructions for maintenance personnel located in the protected premises on actions to take when the aerosol fire extinguishing installation is activated.

    44. Features of control of modular installations powder fire extinguishing during operation
    44.1. The list and frequency of maintenance work are determined in accordance with the regulations drawn up by the developer of the MAUPT based on the technical documentation for the components. The requirements of the maintenance regulations for a specific MAUPT must be no lower than the requirements of the standard maintenance regulations (Appendix 42).

    44.2. The GPN checks the availability of entries in the registration log of maintenance and routine repairs of the MAUPT in accordance with the regulations and checks the maintenance of the passport of the pressure vessel (if its availability is necessary, in accordance with PB 10-115-96).

    44.3. Additionally, representatives of the GPN conduct an external inspection of the MAUPT in accordance with clause 34.5 of these recommendations.

    45. Features of system control fire alarm and automation of fire extinguishing installations during operation
    45.1. When checking the organization of operation of the substation and AUP, a representative of the state fire control authorities must:

  • make sure that there is an order (instruction) from the facility administration to appoint a person responsible for the operation of installations and personnel for maintenance and operational round-the-clock monitoring of the substation and automated control system;
  • get acquainted with technical documentation(project, working or as-built drawings, acts of acceptance and commissioning of installations, passports for instruments and equipment, operating instructions for installations, maintenance schedule, list of routine maintenance, logbook for maintenance and installation malfunctions, job descriptions for maintenance and operational personnel, program and methodology for complex testing of installations);
  • check the ability of the duty (operational) and maintenance personnel to work with alarm control panels (boards), as well as their knowledge of the procedure for checking the operability of installations and actions when detectors and devices are triggered;
  • carry out technical condition monitoring, check the performance of the PS and AUP;
  • check the availability and serviceability of telephone communication with the fire station or control panel of the facility.
  • 45.2. When monitoring the technical condition, conduct an external inspection of the equipment (fire detectors and their sensitive elements, protective nets and glass must be cleaned of dust). Check the presence of seals on the elements and assemblies to be sealed.

    45.3. The orientation of the PI flame must correspond to the design.

    45.4. When checking performance, the GPN representative must:

  • make sure that the detectors are triggered and the corresponding notifications are issued to the control panel and control signals from the control panel;
  • verify the functionality of the PS loop along its entire length by simulating a break or short circuit at the end of the PS loop, and also check the serviceability of the starting electrical circuits;
  • make sure it works control panels, as well as control devices together with peripheral devices (sounders, actuators).
  • 45.5. Checks according to clause 45.4 must be carried out by persons responsible for operating the systems.

    Operating instructions for fire extinguishing systems, APS, SOUE based on the Korund 1I control panel

    I approve

    ______________________________________________________

    INSTRUCTIONS

    for the operation of fire extinguishing systems, fire alarms and warning people about fire at the address: ___________________________________________________________

    Control Panel "Corundum 1I"

    1. 1. General part.
    2. 2. The fire alarm system is designed to detect and notify about the occurrence of a fire.

    2.1. The system must be in standby mode 24/7.

    3. Responsibilities of the shift supervisor to maintain the PS installation in working order.

    3.1. The shift supervisor is required to conduct an external inspection of all protected premises for damage installed equipment and instruments.

    3.2. Monitor all malfunctions and system activations, report them to the head of the unit and the security officer on duty at the checkpoint.

    4. Operation of the system during a fire.

    Actions of the shift supervisor when the control panel "Corundum 1 I" is triggered

    On the front panel of the device there are light indicators (LEDs red and yellow) indicators state of alarm loops from 1 to 4 are not glowing LEDs correspond to the on state of the alarm loops, power indicator " NET» backup power indicator « RESERVE" red from states 1 to 4 " FIRE» train.

    Control buttons: « NET» switching on the 220 V power supply and 24 V DC backup power supply, toggle switches for disabling alarm loops from 1 to 4 button « CONTROL" to check the device in the " mode SELF-CONTROL", button " SOUND" to turn off the sound signal, buttons, button " RESET» to restore the state of the loops after triggering. Toggle switches for turning off (turning on loops) and toggle switches for turning off (turning on) ASPT systems are covered with a protective casing.

    When the devices are working properly and the fire alarm loops are working properly, LEDs 1 to 4 on the linear units and on the instrument panel are off and the LED is on green, the reserve LED is on.

    In the event of a malfunction in a loop (or several loops), the yellow LED “ FAULT» on the corresponding linear unit and on the instrument panel. The device produces a characteristic intermittent fault signal on the device remote control.

    IN in this case disable the button SOUND", open the protective casing of the linear units, turn off the toggle switch of the corresponding loop, press the button " RESET» to restore the “standby” state of the device, make a record of the time of the malfunction and record the number of the faulty loop in the operational log, report to management and call representatives of the organization performing maintenance of the alarm system.

    If the device is triggered by fire detectors in the “ FIRE", the red LED lights up " FIRE» of the corresponding loop(s), a characteristic continuous sound signal sounds on the device, and the remote sounder in the corridor turns on. In this case, turn off the sound signal of the device (the button on the panel " SOUND") check the premises of the corresponding plume for no signs of combustion, if the event is confirmed " FIRE» Call the fire brigade by phone. 01 and, to the extent possible, take measures to extinguish the fire using available fire extinguishing means.

    At the same time, report to the head of the unit and call the checkpoint, inform the security officer on duty about the fire.

    In case false alarm: open the protective casing of the linear units, turn off the toggle switch of the corresponding loop, press the button " RESET» to restore the “standby” state of the device, make a record of the time of the malfunction and record the number of the faulty loop in the operational log, report to the head of the department and call representatives of the organization performing maintenance of the alarm system.

    If the main power supply of the device is turned off, the backup power supply of the device remains on, which will be indicated by the red LED “ RESERVE" After restoring the main power to the device, call a service representative to check and recharge, if necessary, the battery.

    About the serviceability of the backup power supply and battery. batteries are signaled by LEDs " NET" red and " ACC. BAT." green on backup source nutrition.

    Responsible person for fire automatics


    RD 34.49.502-96

    ORGRES


    Chief engineer A.D. Shcherbakov

    Approved Department of Science and Technology RAO "UES of Russia" 04/17/96

    Chief A.P. BERSENEV


    This Instruction sets out the basic requirements for the operation of stationary automatic foam fire extinguishing installations installed at energy enterprises.

    A schematic diagram of a fire extinguishing installation is given. The storage conditions for foam concentrates and their aqueous solutions are described. The technical requirements for the operation of equipment for fire extinguishing installations in general and their individual elements are outlined.

    The procedure for organizing testing and acceptance into operation of newly installed fire extinguishing installations and the regulations for conducting inspections of the technical condition of equipment, equipment and instruments of the fire extinguishing installation and the timing of the audit of the entire installation have been determined.

    Typical malfunctions that may occur during the operation of a fire extinguishing installation are described and recommendations for their elimination are given.

    The basic safety requirements for the operation of foam fire extinguishing installations are indicated.


    The forms of washing acts and hydraulic test pressure and distribution pipelines of fire extinguishing installations, form of logbook for maintenance and repair of fire extinguishing installations, form of fire test report.

    With the publication of this Instruction, the “Instructions for the operation of fire extinguishing installations using air-mechanical foam” (M: SPO Soyuztekhenergo, 1980) becomes invalid.

    1. INTRODUCTION

    1.1. Air-mechanical foam is the most effective fire extinguishing agent for extinguishing class A fires (combustion solids) and B (combustion of liquid substances).

    1.2. To obtain air-mechanical foam, foam concentrates and fire fighting equipment are used. Depending on the area of ​​application, foam concentrates are divided into two classification groups: general purpose and special purpose. To foam concentrates general purpose include: PO-3NP, PO-3AI TEAS. Foaming agents for special purposes include: “Sampo”, “Morskoy”, “Potok”, “Film-forming”, “Foretol”, “Universal”, POF-9M.


    Special purpose foam concentrates differ from general purpose foam concentrates in their higher fire extinguishing ability due to the use of recycled additives.

    All foaming agents for general and special purposes do not lose their original physical and chemical properties during repeated freezing and subsequent gradual thawing.

    Energy plants mainly use general purpose foaming agents.

    1.3. To extinguish fires at transformers and reactors, low-expansion air-mechanical foam is used, and at fuel oil and oil industries, medium-expansion foam is used.

    Low expansion foam is obtained using OPDR foam sprinklers and its modifications.


    NKR - concentrated solution pump;

    OPDR - rosette foam deluge sprinkler;

    GPS - medium expansion foam generator;

    GPSS - stationary medium expansion foam generator;

    Main control room - main control panel;

    PU - control panel;

    KR - concentrated solution;

    PO - foaming agent;

    PI - fire detector;

    OK - check valve;

    Control room - block control panel.

    2. GENERAL PROVISIONS

    2.1. This Instruction is the main technical document used for the development of local instructions for the operation of specific air-mechanical foam fire extinguishing installations installed at energy enterprises.

    2.2. Local operating instructions for a specific fire extinguishing installation with air-mechanical foam are developed by the organization that set up this installation, together with the energy enterprise where it is used. If the adjustment was carried out by an energy enterprise, then the instructions are developed by the personnel of this enterprise.

    2.3. When developing local instructions, in addition to this Instruction, it is necessary to take into account the requirements of design and technical documentation for equipment, devices and equipment included in the fire extinguishing installation.

    2.4. The local instructions must include relevant labor protection requirements and environmental measures to ensure safe operation, technical supervision and repair work at a specific fire extinguishing installation for personnel.

    2.5. Local regulations must be revised at least once every three years and each time after reconstruction of a foam fire extinguishing installation or in the event of a change in operating conditions.

    3. SAFETY MEASURES WHEN OPERATING THE AUPP

    3.1. All rotating parts of PPT, NKR pumps must be enclosed with protective covers.

    Cleaning or wiping pumps while they are in operation is prohibited.

    3.2. The electrical equipment of the pumps must have proper stationary grounding.

    3.3. Putting the equipment into operation, operations with fittings, sampling of the concentrated foaming agent and its solution must be carried out by at least two persons from the service areas.

    3.4. When working with foaming agents, precautions should be taken. Contact of concentrated foaming agent on unprotected skin causes irritation. Exposure to the mucous membrane of the eyes leads to irritation and burns.

    Work with foaming agents should be carried out in rubberized gloves, and eyes and face should be protected with protective shields or goggles.

    If the foaming agent gets on the skin, and especially on the mucous membrane of the eyes, they should be quickly rinsed with plenty of running water.

    3.5. Repair work on the foam fire extinguishing station and on the system should be carried out only according to the order.

    3.6. During the period of personnel stay in the cable rooms (walk-through, repair work, etc.), the start-up of the fire extinguishing installation is switched to remote control mode. Upon completion of work in the protected premises, the automatic operating mode of the foam fire extinguishing installation is restored.

    3.7. When operating the technological equipment of foam fire extinguishing installations, energy enterprise personnel must comply with the established safety requirements set out in the PTE, PPB, PTB and in the factory passports and operating instructions for specific equipment.

    3.8. It is prohibited to pour foaming agent and its solutions into sewer systems and storm drains.

    4. ORDER OF OPERATION OF AUPP

    4.1. An automatic foam fire extinguishing installation (AUPP) is designed to extinguish fires in protected premises and structures of an energy enterprise upon receiving a signal about its occurrence from fire detectors.

    All equipment must be painted in standard colors and clearly labeled.

    4.2. Schematic diagram Fire extinguishing installations using air-mechanical foam are shown in the figure.

    Fundamental technological scheme fire pumping station with finished supply foaming agent solution:

    1 - storage tanks for foam solution; 2 - pumps for supplying foam solution; 3 - pumps for supplying foam concentrate to the tank, foam concentrate solution to the pulse device, circulation of solution, foam concentrate; 4 - pulse device (pneumatic tank); 5 - compressor;

    Gate valve; - check valve.

    Pipelines: foam solution

    water supply

    foaming agent

    solution circulation

    compressed air

    To characterize foam generators or foam sprinklers when various modes work, in the fire extinguishing installation diagram it is recommended to install a special outlet on the pressure pipeline between the pump and the valve closest to the pump, equipped at the end with a valve and a device for connecting a foam generator or foam sprinkler.

    4.3. The automatic foam fire extinguishing installation includes the following main equipment:

    a container for storing foam concentrate or a reservoir for storing an aqueous solution of foam;

    source of water supply (special reservoir or water supply);

    pipeline network;

    pumps for collecting and supplying water or a ready-made aqueous foam solution;

    shut-off and starting devices;

    system automatic control(including fire alarm);

    foam generators or foam sprinklers;

    electrical measuring instruments.

    In addition to the listed main equipment, the automatic control system may include:

    metering pumps for supplying the calculated amount of foam concentrate into pressure and distribution pipelines;

    a water tank for filling feed pumps;

    pneumatic tank to maintain constant pressure in the automatic transmission network;

    compressor for replenishing the pneumatic tank with air.

    4.4. Before filling the foam solution storage tanks, they must be inspected and cleaned internally. After this, use pumps to fill the container with water and concentrated foaming agent in proportions to obtain the required composition of the foaming agent solution.

    4.5. Turn on the foam fire extinguishing pump for recirculation to mix the solution in the tanks for 15 - 20 minutes. At the same time, the following is monitored: leakage of the solution through the water indicator glasses of the tanks, the absence of leaks in the circuit, and the level of the foaming agent in the tanks.

    After this, the solution is analyzed and recorded in the operational log.

    4.6. The launch of the automatic propulsion system must be automatic. Switching the foam extinguishing installation to remote and manual switching mode is not allowed, except in cases of repair work of the installation.

    Automatic start is carried out from the impulse of fire detectors installed in protected premises (structures).

    4.7. Remote start of the automatic control unit is carried out by a button or manual switch key installed on special panels or cabinets of the control panel (main, block, thermal, etc.). Remote start is provided to duplicate automatic start.

    4.8. Devices for local start-up of a fire extinguishing installation are located in the pumping station room and at the control units of distribution pipelines and are intended for testing and setting up a fire extinguishing installation, as well as for starting the installation in the event of automatic and remote start failures.

    4.9. The control panel should contain a diagram of this installation with brief description devices and operation of automatic control devices. The pumping station premises must contain instructions on the procedure for putting pumps into operation and opening shut-off valves, as well as a schematic and technological diagram.

    4.10. Control units and automatic control equipment must have appropriate visual diagrams, inscriptions and signs.

    4.11. To obtain air-mechanical foam of medium expansion, foam generators GPS-200, GPS-600 and GPS-2000 are used, technical specifications which are given in table. 1.

    Table 1

    4.12. The brand of foam generator or foam sprinkler is determined by the project, taking into account the design features of the object being protected, the fire load and the efficiency of supplying the fire extinguishing agent to the fire.

    4.13. Upon completion of the foam fire extinguishing installation's operation to extinguish a fire in the protected area, it must be inspected. If mechanical damage is detected on pipelines, shut-off and starting devices, foam generators and other equipment, they must be repaired as soon as possible.

    4.14. To obtain low expansion air-mechanical foam, OPDR-15 sprinklers are used, the technical characteristics of which are given in table. 2.

    Table 2

    Pressure, MPa

    Consumption, l/s

    Foam ratio

    Foam durability, s

    Conditional radius of irrigation, m

    Irrigation area, m2

    Irrigation intensity per solution, l/s?m2

    Irrigation intensity by foam, l/s?m2

    solution

    Note. Indicated in the table. 2 data are given for a sprinkler located 3.5 m from the irrigation surface.

    5 . STORAGE OF FOAMING AGENT AND AQUEOUS SOLUTION OF FOAMING AGENT

    5.1. Foaming agents and their aqueous solutions are recommended to be stored at a temperature no higher than 20 °C and no lower than 5 °C, which ensures the longest shelf life.

    5.2. When a concentrated foaming agent arrives at an energy company, it is necessary to ensure that there is a document certifying its quality and quantity.

    After this, a scheme for filling the containers is prepared and the pump is turned on to pump the concentrated foaming agent. Upon completion of pumping the foam concentrate, the original recirculation scheme is restored.

    5.3. Before refueling the automatic propulsion system, it is necessary to check the quality of the foam concentrate or its ready solution according to the methodology given in the work “Procedure for use, transportation, storage and quality control of foam concentrates for extinguishing fires. (Instructions)." M.: VNIIPO Ministry of Internal Affairs of the USSR, 1989). The analysis of the foam concentrate solution is carried out in the laboratory of the energy company.

    In the future, the quality of the foam concentrate or its aqueous solution in the automatic production unit should be checked once every six months.

    If the expansion ratio of the foam obtained in laboratory conditions is less than 5 or its stability is less than 3 minutes, replace the foam agent and its aqueous solution.

    An unsuitable foaming agent solution according to an appropriate scheme can be supplied through steam-mechanical fuel oil nozzles into the furnaces of operating combustion boilers, or disposed of in another way that does not contradict environmental requirements.

    5.4. After the automatic control device has been activated, further use of the foaming agent or its aqueous solution is permitted depending on the amount of residue and its quality. The remaining foaming agent or its aqueous solution must not be mixed with other brands of foaming agent. Before filling the container with a new foaming agent, it is necessary to check its quality if it has not been checked for more than 3 months.

    5.5. Storing foam concentrates in reinforced concrete tanks is not recommended.

    Clean water supplies can be stored in concrete, reinforced concrete, metal and other tanks.

    5.6. Tanks for storing reserves of an aqueous solution of foaming agents or water must be equipped with automatic level meters with readings displayed on the control panel.

    5.7. Checking the level of the aqueous solution of the foaming agent or water must be carried out daily and recorded in the “Logbook for the maintenance and repair of the fire extinguishing installation.”

    If the level of the foaming agent aqueous solution or water decreases due to evaporation, water should be added. If there are leaks, locate the damage to the tank and repair the leaks, then check the quality of the remaining foam concentrate.

    5.8. The prepared aqueous solution of foaming agents in tanks and in the pipeline network must be mixed at least once every three months.

    5.9. The water for preparing the solution and the solution must not contain mechanical impurities that can clog pipelines, throttle washers and steam generator screens. The water for preparing the spread must meet the requirements for drinking water.

    5.10. To prevent decay and blooming of water, it is recommended to disinfect it with bleach at the rate of 100 g of lime per 1 m 3 of water. The prepared aqueous solution of the foaming agent cannot be disinfected.

    5.11. The water in the tank must be replaced annually. When replacing water or a ready-made aqueous solution of a foaming agent, the bottom and inner walls of the tank are cleaned of dirt and growths, the damaged color is restored or completely renewed.

    6. TECHNICAL REQUIREMENTS FOR OPERATION OF AUPP EQUIPMENT

    6.1. General requirements

    6.1.1. The entrances to the building (premises) of the pumping station of the fire extinguishing installation, as well as approaches to pumps, compressors, control units and other equipment of the automatic fire extinguishing installation, must always be free.

    6.1.2. The pumping room must be provided with telephone communication with the main control room (MCR) and emergency lighting.

    6.1.3. The following must be sealed at the current automatic control point:

    valves on pipelines on the suction side of installation pumps, on pressure and distribution pipelines;

    hatches of water storage tanks or aqueous foam solution;

    valves (with manual control and electric drive) in control units;

    manual taps;

    safety valves;

    pressure switch.

    6.1.4. After activation of the automatic control system, its functionality must be fully restored no later than 24 hours. “Dry pipes” that were filled with an aqueous solution of a foaming agent must be washed or blown with compressed air.

    6.1.5. Threaded connections AUPP should be compacted with combed flax (without bonfire), soaked in grated red lead or white on natural drying oil. The use of hemp and natural drying oil substitutes for this purpose is not allowed, since foaming agents have high penetrating properties.

    6.2. Tanks for storing foaming agent, ready-made foaming agent solution

    6.2.1. When replacing a foam concentrate, the container (reservoir) must be cleaned and steamed until traces of the old foam concentrate are removed.

    6.2.2. The serviceability of the automatic level gauge in tanks (containers) must be checked at least once every three months at positive temperatures and immediately in case of doubt about the proper operation of the level gauge.

    6.2.3. Tanks must be closed to unauthorized persons and sealed; the integrity of the seal is checked once a quarter.

    6.2.4. IN winter period for buried tanks, the gap between the lower and upper hatch covers must be filled with insulating materials.

    6.2.5. The enterprise must have a double supply of foam concentrate available for foam fire extinguishing installations.

    6.3. Pipelines

    6.3.1. Pipelines of fire extinguishing installations must have a slope of at least 0.01 for pipe diameters up to 50 mm and at least 0.005 for pipe diameters greater than 50 mm. Sagging and bending of pipelines is not allowed.

    6.3.2. If there are reverse slopes (bags) on the pipelines, drainage devices must be installed in these places.

    6.3.3. Welding pipelines directly to metal load-bearing structures buildings and structures and elements of technological equipment are not allowed.

    6.3.4. Each pipeline bend of more than 0.5 m must have a fastening. The distance from hangers to welded and threaded joints of pipes must be at least 100 mm.

    6.3.5. Once every three years, as well as after completion of installation and repair work, pipelines must be flushed and subjected to hydraulic tests with the drawing up of a report (Appendices 2 and 3).

    6.3.6. Flushing of pipelines should be carried out by supplying water towards the control units of the automatic control unit and then discharging the water into the sewer system (fire hoses can be used to supply and discharge water). During flushing, foam generators or foam sprinklers are removed, and plugs or plugs are installed in the holes.

    6.3.7. Flushing of pipelines must be carried out at a water speed that ensures the removal of sediment (at least 1.5 m/s), and continue until clean water appears.

    6.3.8. If it is impossible to flush pipelines in certain sections of the network, purging with compressed air or inert gas is allowed.

    6.3.9. Hydraulic testing of pipelines is carried out at a pressure equal to 1.25 working pressure (P) (but not less than P + 0.3 MPa). After 10 minutes of testing, the pressure is gradually reduced to working pressure and all welded joints and adjacent areas are carefully inspected. Pressure measurement should be carried out using two pressure gauges (one of which is control).

    6.3.10. During hydraulic tests, the presence of unauthorized persons is prohibited. Personnel involved in testing must be in safe areas.

    6.3.11. The pipeline network is considered to have passed the hydraulic test if the following is not detected:

    signs of rupture;

    fistulas on welded joints and pipelines;

    external mechanical deformations.

    6.3.12. Flushing and hydraulic testing of pipelines must be carried out under conditions that eliminate the risk of freezing. Backfilling of individual trenches (in which pipelines are laid) that have been exposed to severe frosts, or backfilling of trenches with pipelines with frozen soil is prohibited.

    6.3.13. Once a quarter, the condition of the inputs, shut-off valves, measuring instruments and water intake well is checked.

    6.3.14. Before the onset of cold weather, the fittings in the water intake well must be inspected, repaired and insulated.

    6.3.15. Once a quarter the following is checked:

    absence of leaks and deflections of pipelines;

    condition of pipeline fastening;

    no contact with electrical wires and cables;

    condition of paint and absence of dirt and dust.

    Detected deficiencies that may affect the reliability of the automatic transmission system must be eliminated immediately.

    use of UAP pipelines for hanging or fastening any equipment;

    connection of production pipelines and equipment.

    6.4. Pumping station

    6.4.1. Once a month, the pumps and other equipment of the pumping station are inspected, cleaned of dust and dirt, the operation of the automation and the transfer of all pumps to the main and backup power supply are checked, with the results being recorded in the operational log.

    6.4.2. Before testing the pumps, it is necessary to check: the tightness of the seals; presence of lubricant in bearing baths; correct tightening of foundation bolts, pump cover nuts and bearings; connections of pipelines on the suction and discharge sides with pumps; serviceability of couplings and their guards; proper grounding; filling the pipelines on the suction side and the pumps themselves with water.

    6.4.3. The tank for filling pumps with water must be inspected, repaired and painted annually.

    6.4.4. Pumps and motors must be inspected once every three years. The audit, as well as the elimination of detected deficiencies, must be carried out in a short time.

    Repair and replacement of worn-out parts and overhaul of oil seals are carried out as necessary.

    6.4.5. The pumping station premises must be kept clean and locked. One of the spare keys must be stored on the control panel, which must be indicated on the main control room door.

    6.5. Control nodes

    6.5.1. The condition of control units, the position of shut-off valves, pressure values ​​before and after control units must be monitored at least once a month.

    6.5.2. Each control unit must have a sign indicating the name of the protected object and a functional diagram of the wiring.

    6.5.3. Control units must be located in rooms with a minimum air temperature throughout the year not lower than 4 °C.

    6.5.4. Maintenance of control units involves cleaning the holes (especially small diameters) and checking their operation. In the room where the control units are located, the temperature must be maintained at least 5 °C.

    6.5.5. Once every six months, the operation of the control unit is checked with its automatic activation from the fire detector when the valve on the “dry pipe” is closed, and the reliability of the operation of all parts of the unit is also checked.

    6.5.6. Repair and replacement of worn out and broken parts, replacement of rubber diaphragms and gaskets, reassembly of oil seals, gate valves and valves are carried out as necessary.

    6.5.7. In shut-off and start-up devices, steel fittings should be used - electrified valves with automatic start-up with a working pressure of 1.6 MPa; repair valves with manual drive with a working pressure of 1.6 MPa.

    6.5.8. The reliability of operation and tightness of gate valves, valves and check valves should be checked at least once a month.

    6.5.9. All damage to valves, valves and check valves that may affect the reliability of the installation must be repaired immediately.

    6.6. Foam generators and foam sprinklers

    6.6.1. Before installation, each foam generator and foam sprinkler must be thoroughly cleaned of preservative lubricant and subjected to a hydraulic test at a special outlet at a pressure of 1.25 working.

    A repeated hydraulic test is carried out after three years under normal conditions, and annually if there are traces of corrosion.

    6.6.2. Detected damage to foam generators and sprinklers - rupture of the mesh, flying out of the sprayer socket, deformation of the body, paint or solution getting onto the mesh and into the hole, clogging of the mesh and holes with scale, fire damage during a fire - must be immediately repaired.

    6.6.3. In stationary foam extinguishing conditions, the use of sprayers made of nylon and other flammable materials on foam generators is not allowed.

    6.6.4. In places of possible mechanical damage, foam generators and sprinklers should be protected with metal mesh, which should not be in the path of foam exit.

    6.6.5. Foam generators and foam sprinklers should be inspected and cleaned of dust and dirt once a month. If corrosion is detected, measures must be taken to eliminate it.

    6.6.6. In case of repair work at the installation sites of foam generators or foam sprinklers, the grids of the foam generators and the holes of the sprinklers must be protected from plaster and paint (for example, with polyethylene or paper caps, etc.). Traces of paint and mortar found after repair must be removed.

    6.6.7. To replace faulty or damaged foam generators or foam sprinklers, a reserve of 10 - 15% of the total number of installed foam generators and sprinklers must be created.

    install plugs and plugs instead of faulty sprinklers;

    store materials and equipment at a distance of less than 0.9 m from sprinklers.

    6.7. Air tank and compressor

    6.7.1. Putting the pneumatic tank into operation must be done in the following sequence:

    fill the pneumatic tank with an aqueous solution of a foaming agent to approximately 50% of its volume (the level is controlled by the water meter glass);

    turn on the compressor or open the valve on the compressed air pipeline;

    raise the pressure in the pneumatic tank to the working pressure (controlled by a pressure gauge), after which the pneumatic tank is connected to the pressure pipelines, creating working pressure in them.

    6.7.2. An external inspection of the air tank should be carried out daily, the level of the foam concentrate solution and the air pressure in the air tank should be checked. When the air pressure decreases by 0.05 MPa (relative to the working one), it is pumped up.

    The compressor should be tested at idle once a week.

    6.7.3. Maintenance of the air tank and compressor, carried out once a year, includes:

    draining, inspecting and cleaning the air tank;

    removing and testing the operation of the safety valve on a bench (replace with a new one if it malfunctions);

    painting the surface of the air tank (the date of repair is indicated on the surface);

    detailed inspection of the compressor (worn parts and fittings are replaced);

    implementation of all other technical measures provided for by the factory passports and operating instructions for the air tank and compressor.

    6.7.4. The inspection of the pneumatic tank is carried out by a special commission with the participation of representatives of Gosgortekhnadzor and local authorities fire department Ministry of Internal Affairs of Russia and this energy enterprise.

    6.7.5. The use of compressors to provide compressed air to any other equipment is prohibited.

    6.7.6. The compressor must be started manually and the level in the air tank must be monitored.

    6.7.7. The accuracy of the readings of pressure gauges installed on pneumatic tanks is checked once a month, and all other pressure gauges - once every six months. All installation pressure gauges are checked using a control pressure gauge.

    6.7.8. Checking pressure gauges and sealing them must be carried out annually in accordance with the current regulations.

    6.7.9. Personnel allocated to servicing compressors and pneumatic tanks of automatic propulsion units must be trained and certified in accordance with the requirements of the rules of Gosgortekhnadzor.

    7. PROCEDURE FOR ACCEPTANCE AND MAINTENANCE OF AUPP

    7.1. The diagram, characteristics of the equipment and devices of the fire extinguishing installation (pumps, air compressors, water pressure or pneumatic tanks, water supply networks, control units, check valves, drain valves, pressure gauges, vacuum gauges, foam generators, foam sprinklers, etc.) must correspond to the project.

    7.2. Any deviations from the accepted scheme, replacement of pipelines, materials, equipment or devices during installation work or during operation of the fire extinguishing installation must be previously agreed upon with the design organization.

    7.3. Upon completion of the installation of the automated control system, the energy enterprise must organize, with the participation of representatives of the installation and commissioning organizations and the local fire department of the Ministry of Internal Affairs of Russia, a quality check of the work, compliance of the installation with the design documentation, based on the results of which a working report or protocol is drawn up.

    7.4. The commissioning of a fire extinguishing installation is carried out by a commission specially appointed for this purpose according to a program developed by the design institute - the author of the installation project and approved by the chief technical manager of the energy enterprise. In addition to representatives of the energy company, installation organization and the design institute, representatives of the fire department of the Ministry of Internal Affairs of Russia should be included in the commission.

    The commission must be presented with the necessary technical documentation: the installation design with the amendments; factory certificates and operating instructions for equipment, devices and equipment included in the installation; acts for hidden work, inspection of installation work, flushing and hydraulic testing of pipelines and vessels, testing, as well as operating instructions for the fire extinguishing installation.

    7.5. The reliability and effectiveness of the fire extinguishing installation is checked by testing it according to a program agreed upon with the local fire protection authorities of the Ministry of Internal Affairs of Russia and approved by the chief technical manager of the energy enterprise. It is recommended to conduct fire tests of the operation of the automatic propulsion system. The test results are documented in a report; the form of the test report is given in Appendix 4.

    7.6. The technical capabilities of the automatic fire control unit to detect and extinguish a fire should be included in the operational fire extinguishing plan of a given energy enterprise. During fire drills, it is necessary to familiarize personnel with the purpose, structure and operation of the automatic fire control system.

    7.7. The head of the energy enterprise appoints a person responsible for the operation of the automatic control unit and personnel to carry out maintenance and repair of the installation.

    7.8. At the energy enterprise, the person responsible for the operation of the automated control system must have the following documentation available:

    design documentation and as-built drawings for installation;

    certificates of acceptance and commissioning of the installation;

    passports for equipment and instruments;

    list of installed equipment, components, devices and automation equipment;

    maintenance and repair schedule;

    plant maintenance and repair log.

    7.9. The person responsible for operating the automatic propulsion system must conduct appropriate training once a month with the personnel allocated to service this installation.

    7.10. To carry out work on maintenance and repair of the automated control system at the energy enterprise, it is necessary to create the necessary stock of equipment, components and devices of the automated control system, for the storage of which a special room must be allocated.

    7.11. The operation of the automatic control unit should be checked during the process plant (equipment) being taken out for repair or maintenance.

    7.12. When the automatic fire control unit is disconnected for repairs or inspection, it is necessary to notify the relevant fire department in advance.

    7.13. Each automatic control unit must be in constant readiness for action. Each case of an accident or failure in its operation must be thoroughly investigated and the causes and those responsible for the accident (failure) must be identified.

    8. CHARACTERISTIC MALFUNCTIONS IN THE OPERATION OF AUPP AND RECOMMENDATIONS FOR THEIR ELIMINATION

    Table 3

    Nature of the malfunction, external signs

    Foam and water do not come out of the foam generator or sprinklers, the pressure gauge shows normal pressure

    The valve is closed

    Open the valve

    Check valve stuck

    Open check valve

    The main line or the pressure and distribution pipelines are clogged

    Clean the main or distribution pipeline

    Foam generators or foam sprinklers are clogged

    Clear the blockage

    Only water comes from foam generators or sprinklers

    Foaming agent has leaked from the container or dispenser tank.

    Fill the container or dosing tank with foaming agent

    The metering pump did not turn on

    Check the operation of the metering pump

    One of the valves on the dosing tank is closed

    Check the serviceability and opening of the valves

    The inlet or outlet pipe on the dosing tank is clogged

    Clean the inlet or outlet pipe

    The dosing washer is clogged

    Clean the dosing washer

    Clean foaming agent flows from foam generators or sprinklers

    The feed pump did not start working

    Turn on the feed pump

    The valve on the pipeline on the suction side of the feed pump is closed

    Open the valve

    There is an air leak on the suction side of the feed pump

    Troubleshoot connection problems

    Wrong direction of rotor rotation

    Switch motor phases

    A valve in the other direction is accidentally opened

    Close the valve in the other direction

    Foam ratio is lower than calculated

    Poor quality foaming agent

    Replace foam agent

    The concentration of the foaming agent in the solution is lower than the calculated one

    Increase the concentration of the foaming agent

    The pressure of foam generators is less than 0.4 or more than 0.6 MPa

    Ensure the pressure at the foam generator is not less than 0.4 and not more than 0.6 MPa

    Foam is supplied intermittently

    Water flow changes in pressure and distribution pipelines

    Provide the calculated water flow and pressure

    Leakage of an aqueous solution of foaming agent or water through welded seams at the connection points of control units of foam generators or sprinklers

    Poor quality welding

    Check the integrity of the welds

    The gasket is worn out

    Replace gasket

    Loose bolts

    Tighten the bolts

    No pressure gauge reading

    There is no pressure in the pipeline

    Restore pressure in the pipeline

    The inlet is clogged

    Remove the pressure gauge and clean the hole

    Sparking pressure gauge contacts

    Contamination of pressure gauge contacts

    Remove the pressure gauge glass and clean the contacts

    Appendix 1

    EXTRACT FROM THE WORK “ORDER OF APPLICATION, TRANSPORTATION, STORAGE AND QUALITY CHECKS OF FOAMING AGENTS FOR FIRE FIGHTING. (INSTRUCTIONS)"

    TESTING METHODS FOR FOAMING AGENTS

    1 . DETERMINING APPEARANCE

    1.1. Appearance The foaming agent is determined visually in a test tube made of colorless glass P2 with a diameter of 30 mm and a capacity of 250 cm 3 (GOST 253336-82) in transmitted scattered light.

    1.2. To determine the crystalline precipitate, a foaming agent pre-filtered at 20 ° C is poured in an amount of 250 cm 3 into a cylinder with a capacity of 250 - 500 cm 3 and placed in a refrigerator at a temperature of (3 + 2) ° C. After 24 hours of exposure there should be no formation of crystalline sediment visible to the naked eye.

    2 . DETERMINATION OF PORNING TEMPERATURE

    2.1 . Equipment

    Test tube P2T-250 TS according to GOST 25336-82;

    test tube P1-16-150 HS according to GOST 25336-82;

    mercury thermometer type TN-6 according to GOST 400-80;

    vessel with a cooling mixture.

    2.2 . Carrying out tests

    A clean, dry glass tube with a diameter of 16 mm is filled with foaming agent to a height of 30 mm. The test tube is closed with a stopper with a thermometer inserted into it and placed in a test tube with a diameter of 30 mm so that the walls of the test tube are at the same distance from the walls of the coupling.

    The assembled device is placed in a vessel with a cooling mixture, the temperature of which should be 5 °C below the expected freezing temperature of the foam concentrate.

    The pour point is taken to be the value established after the decline and rise.

    2.3 . Processing the results

    Determination of the pour point is carried out 3 - 4 times. The final result is the arithmetic mean of all determinations.

    3 . DETERMINATION OF FOAM EXPANSION AND STABILITY IN LABORATORY CONDITIONS

    3.1 . Equipment, reagents

    Device “Tissue Shredder” (RT-1) according to TU 64-1-1505-79. A graduation must be applied to the instrument glass with a division value of 50 cm 3 to the final value of 1000 cm 3.

    Cylinder 2-100 according to GOST 1770-74.

    Stopwatch according to GOST 5072-79, accuracy class 3.

    Distilled water according to GOST 6709-72.

    3.2 . Carrying out tests

    The foaming agent in the amount necessary to obtain a concentration solution is poured into the cylinder and adjusted with distilled water to 100 cm 3 . The resulting foaming agent solution at a temperature of (18 + 1) °C is poured into the glass of the device, the speed switch is set to 4000 rpm, then the electric motor and stopwatch are turned on simultaneously. The solution is stirred for 30 s, the electric motor is turned off and the volume of the resulting foam in the glass is recorded.

    The foam multiplicity is calculated as the ratio of the resulting volume (in cm 3) of foam to 100 cm 3 of the solution taken for testing. The stability of the foam is determined by the time it takes for 50% (50 cm3) of the foaming agent solution to be released from it.

    The arithmetic mean of three determinations of the foam ratio is taken as the test result.

    3.3 . Determination of foam stability on the surface of ethyl alcohol

    3.3.1 . Instruments and reagents used

    General purpose laboratory scales, maximum weighing limit 200 g.

    Glass glass according to GOST 25336-82, type VN-400, capacity 400 ml.

    Measuring cylinder according to GOST 17770-74, accuracy class 2, capacity 100 ml.

    Glass rod, diameter 4 - 8 mm, length 150 - 250 mm.

    Mechanical stopwatch according to GOST 5072-79, class 2, measurement limit 60 min.

    Rectified ethyl alcohol according to GOST 5962-67 or technical alcohol according to GOST 18300-87.

    3.3.2 . Carrying out tests

    Measure 100 ml of ethyl alcohol with a cylinder and place it in a glass, which is placed on a scale. Foam (obtained in accordance with the requirements of clause 6.2) is applied to the surface of the alcohol in an amount of (8 + 0.5) g. In the event of the formation or destruction of foam in the process of open areas of the surface of the alcohol or peeling of the foam when large air bubbles form, it should be leveled with a glass rod foam over the entire surface of the alcohol, without touching the separating gel-like film.

    A stopwatch records the time from the moment the first portion of foam is applied to the alcohol until open areas of the surface of the alcohol or separating film appear. This time determines the stability of the foam on the surface of the alcohol. The test is carried out three times. The arithmetic mean is taken as the final result.

    4 . DETERMINATION OF FOAM EXPANSION ON A MEDIUM EXPANSION FOAM GENERATOR

    4.1 . Equipment, materials, reagents

    Generator GPS-200 or GPS-600 according to GOST 12962-80.

    A pump providing a solution supply of at least 2 dm 3 /s for (GPS-200) or at least 6 dm 3 /s for (GPS-600) at a pressure in front of the foam generator of 0.6 - 1.0 MPa.

    Fire pressure flax jute hose with a diameter of 51 mm according to RSFSR TU 40-1069-81.

    Fire suction hose according to GOST 5398-76.

    A metal container with a capacity of at least 200 dm 3 for preparing solutions.

    A metal container of at least 100 dm 3, weighing no more than 10 kg for collecting foam.

    Static weighing scales in accordance with GOST 23676-79 of medium accuracy class with the largest weighing limit of 30 kg.

    Pressure gauge in accordance with GOST 2405-80 with an upper pressure measurement limit of 1.0 MPa, accuracy class 2.5, splash-proof design, installed at the pump outlet.

    Drinking water according to GOST 2874-82.

    4.2 . Carrying out the test

    200 dm 3 of a working solution of a foaming agent is prepared in a container. The prepared solution is fed through a suction hose by a pump under a pressure of 0.6 MPa into a pressure hose, at the outlet of which a generator is installed.

    After obtaining stable foam from the generator, fill the container for collecting foam, and the entire volume must be uniformly filled; The formation of voids is not allowed. Determine the mass of foam in the container by weighing on a scale.

    4.3 . Processing the results

    The foam multiplicity K is determined by the formula:

    where V is the volume of foam, m 3;

    V 1 is the volume of the foaming agent solution in cubic decimeters, numerically equal to the mass of the foam, kg.

    The arithmetic mean of three determinations is taken as the result of the determination.

    Appendix 2

    ACT
    WASHING PIPELINES OF FIRE FIGHTING INSTALLATIONS

    Name of the object _____________________________________________________

    (power plant, substation)

    We, the undersigned ___________________________________________________

    represented by ___________________________________________________________________

    _________________________________________________________________________

    And _______________________________________________________________________

    _________________________________________________________________________

    have drawn up this act that the pipelines ___________________________________

    _________________________________________________________________________

    (installation name, section number)

    Special notes: ___________ : ____________________________________________

    _________________________________________________________________________

    _________________________________________________________________________

    _________________________________________________________________________

    Members of the commission:

    (surname) (signature)

    Assembly

    (surname) (signature)

    Fire department

    Appendix 3

    ACT
    HYDRAULIC TESTING OF PIPELINES OF FIRE FIGHTING INSTALLATION

    _______________ "____"_________ 19__

    (power plant, substation)

    We, the undersigned _____________________________________________________

    represented by _____________________________________________________________________

    (representative from the customer, full name, position)

    And __________________________________________________________________________

    (representative from the installation organization, full name, position)

    have drawn up this report in that when testing pipelines the following results were obtained:

    The installed pipeline network of the stationary fire extinguishing installation is suitable for operation.

    Members of the commission:

    Customer ______________________________ _____________________

    (surname) (signature)

    Assembly

    organization ______________________________ _____________________

    (surname) (signature)

    Fire department

    security ______________________________ _____________________

    (last name, position) (signature)

    Appendix 4

    act
    CONDUCTING FIRE TESTS OF FIRE FIGHTING INSTALLATIONS

    _______________ "____"_________ 19__

    Name of the object ________________________________________________________________

    (power plant, substation)

    We, the undersigned members of the commission consisting of:

    1. From the customer ______________________________________________________________

    (representative from the customer, full name, position)

    ___________________________________________________________________________

    2. From the installation (commissioning) organization _____________________________________

    ___________________________________________________________________________

    (representative from the installation organization, full name, position)

    3. From the fire department ______________________________________________________________

    ___________________________________________________________________________

    (representative from the fire department, full name, position)

    4. _________________________________________________________________________

    ___________________________________________________________________________

    ___________________________________________________________________________

    drew up this act in that in order to check the operability of the installed installation, they carried out fire tests in

    ___________________________________________________________________________

    (name of tested area)

    Artificial fires measuring ____________________________ m2 with combustible material ________________________________________________________________

    As a result of the test, the time was established:

    arson of a fire _________________________________________________ (h, min)

    unit activation __________________________________________ (h, min)

    appearance of water from the foam generator ________________________________ (h, min)

    During fire tests, the installation worked, the room was filled

    foam in _______________ min

    Members of the commission:

    Customer ______________________________ _____________________

    (surname) (signature)

    Assembly

    organization ______________________________ _____________________

    (surname) (signature)

    Fire department

    security ______________________________ _____________________

    (last name, position) (signature)

    Appendix 5

    1. Introduction. 2

    2. General provisions. 2

    3. Safety precautions when operating automatic propulsion systems.. 3

    4. Operating procedure for automatic automatic transmission.. 3

    5. Storage of foaming agent and aqueous solution of foaming agent. 6

    6. Technical requirements for operation of automatic propulsion equipment.. 7

    6.1. General requirements. 7

    6.2. Tanks for storing foaming agent, ready-made foaming agent solution. 7

    6.3. Pipelines.. 8

    6.4. Pumping station. 9

    6.5. Control nodes. 9

    6.6. Foam generators and foam sprinklers. 10

    6.7. Air tank and compressor. 10

    7. The procedure for acceptance and maintenance of automatic control units.. 11

    8. Typical malfunctions in the operation of automatic transmission systems and recommendations for their elimination.. 12

    Appendix 1 Extract from the work “the procedure for using, transporting, storing and checking the quality of foam concentrates for extinguishing fires. (Instructions)." 13

    Appendix 2 Certificate of flushing of fire extinguishing installation pipelines. 15

    Appendix 3 Hydraulic test report for fire extinguishing installation pipelines. 16

    Appendix 4 report of fire testing of fire extinguishing installation. 17

    Appendix 5 Logbook for maintenance and repair of fire extinguishing installations. 17

    Share